Tips for Quick Selection Guide
Walk-In Cooler Box Load Parameters
- 95°F ambient air temperature surrounding box
- 4" styrene (R=16.7, K=.24) walls/ceiling, 6" concrete slab floor
- Average product load with 5°F pulldown in 24 hours
- BTUH load based on 16-18 hour compressor run time for 35°F box (timer recommended)
- See Table C for adjustment to box load for glass doors
- For 80°F ambient temp. surrounding box deduct 12%
- For 4" Urethane walls + ceiling, 6" concrete slab floor deduct 12%
- For 10' ceiling height add 10%
- For additional BTUH load for product cooling see Table A
Walk-In Freezer Box Load Parameters
- 95°F ambient air temperature surrounding box
- 4" urethane (R=25, K=.16) walls, ceiling + floor
- Average product load with 10°F pulldown in 24 hours
- BTUH load based on 18 hour compressor run time
- See Table C for adjustment to box load for glass doors
- For 80°F ambient temp. surrounding box deduct 12%
- For 20 hour compressor run time (light frost load) in lieu of 18 hou run time, deduct 11%
- For 10' ceiling height add 10%
- For additional BTUH load for product cooling see Table D
Table A - Product Cooling Loads for Walk-In Coolers
| Product | Specific Heat | 10 Degree Pulldown BTUH Load | |||||
|---|---|---|---|---|---|---|---|
| 500 | 1000 | 1500 | 2000 | 3000 | 5000 | ||
| Beef | 0.72 | 240 | 480 | 720 | 960 | 1440 | 2400 |
| Pork | 0.53 | 177 | 353 | 530 | 706 | 1060 | 1767 |
| Veal & Lamb | 0.76 | 253 | 506 | 760 | 1012 | 1520 | 2533 |
| Poultry | 0.79 | 263 | 526 | 790 | 1053 | 1580 | 2633 |
| Seafood | 0.80 | 267 | 533 | 800 | 1066 | 1600 | 2667 |
| Vegetables | 0.92 | 307 | 613 | 920 | 1226 | 1840 | 3067 |
| Bakery Food | 0.74 | 247 | 494 | 740 | 988 | 1480 | 2467 |
| Beer | 1.00 | 333 | 666 | 1000 | 1333 | 2000 | 3333 |
| Floor Sq. Ft. | Approx. 65% R.H. Room Temp. | |
|---|---|---|
| 55°F | 50°F | |
| 100 | 93 | 105 |
| 200 | 88 | 99 |
| 300 | 85 | 95 |
| 400 | 81 | 90 |
| 500 | 78 | 87 |
| 600 | 75 | 85 |
| 700 | 72 | 81 |
| 800 | 69 | 78 |
| 900 | 67 | 75 |
| 1000 | 65 | 73 |
| 1200 | 62 | 69 |
| Box Temperature | BTU per Door |
|---|---|
| +35 | 1060 |
| +30 | 960 |
| 0 | 1730 |
| -10 | 1730 |
| -20 | 1730 |
Room loads based on a continuous operation that includes an allowance for the average number of personnel, processing equipment, etc., with a glass panel in one wall and walls and ceilings insulated with 3" of styrene with box located in an air-conditioned area. The evaporator should be low outlet velocity type to avoid drafts and should be selected for continuous operation and not less than 30°F evaporator temperature.
Adjusted for run time load. Multiply number of doors times door load above and add to box load.
Table D - Product Freezing Loads for Walk-In Freezers
| Product | Specific Heat BTU/lb/°F | Latent Heat BTU/lb | Freezer Temp (F) | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| 32 - | 32 + | 100 | 300 | 750 | 1000 | 1500 | 3000 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Beef | 0.72 | 0.40 | 95 | 29 | 790 | 2370 | 5925 | 7900 | 11850 | 23700 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Pork | 0.53 | 0.32 | 60 | 28 | 523 | 1571 | 3926 | 5235 | 7853 | 15710 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Veal & Lamb | 0.76 | 0.45 | 100 | 28 | 841 | 2524 | 6311 | 8414 | 12621 | 25240 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Poultry | 0.79 | 0.42 | 106 | 27 | 878 | 2636 | 6590 | 8787 | 13181 | 26360 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Seafood | 0.80 | 0.43 | 110 | 28 | 906 | 2719 | 6797 | 9063 | 13595 | 27190 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Vegetables | 0.92 | 0.47 | 130 | 30 | 1053 | 3159 | 7898 | 10530 | 15795 | 31590 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Bakery Food | 0.74 | 0.34 | 53 | 20 | 520 | 1560 | 3900 | 5200 | 7800 | 15600 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Freezing loads based on product entering at 40°F maximum. For a specific pulldown time, the product load BTU/hr may be adjusted by multiplying the above loads by 24 and dividing by the specified pulldown time in hours. To adjust for 0°F freezer temperature, multiply the above loads by 0.97, and for -20°F freezer, multiply by 1.04